Abstract
This paper investigates the feasibility of utilising blind bolts as shear connectors to develop demountable steel-concrete beams. The flexural behaviour of composite beams with two blind bolt types and welded stud connectors were experimentally investigated using full-scale beam specimens. A set of push-test specimens was tested based on the Eurocode 4 to compare the slip response of these connectors. The ultimate design loads of the test beams were calculated based on rigid plastic analysis (RPA) using the actual material properties. The beam experiments were simulated by using three-dimensional non-linear finite element models (FEMs). The material behaviour for concrete and steel in FEMs was described using concrete damage plasticity and steel plasticity models respectively. The FEMs were validated by comparing the load-midspan deflection curves of the beam specimens obtained from the experiments and modelling. The effects of the concrete compressive strength, steel yield strength and the shear connection ratio on the flexural behaviour of the composite beams were studied by utilising the validated FEMs. The experimental and numerical results suggest that the ability of the blind bolts to achieve and maintain composite action in steel-concrete beams under flexural loading is comparable to that of the welded stud connectors.
Original language | English |
---|---|
Pages (from-to) | 181-194 |
Number of pages | 14 |
Journal | Engineering Structures |
Volume | 114 |
DOIs | |
Publication status | Published - 1 May 2016 |
Bibliographical note
Publisher Copyright:© 2016 Elsevier Ltd.
Keywords
- beams
- composite construction
- concrete
- sheer connectors